Samsung FJM Air Conditioner Error Codes List

Samsung Multi Air Conditioner Error mode and check method

INDOOR UNIT

FREE JOINT

MH020FVEA MH023FVEA MH026FVEA MH035FVEA MH052FVEA MH020FNEA MH026FNEA MH035FNEA MH052FNEA MH023FBEA MH026FBEA MH035FBEA MH052FBEA MH026FKEA MH035FKEA MH026FSEA MH035FSEA MH030FMEA MH035FMEA MH052FMEA MH023FEEA MH026FEEA MH035FEEA MH052FUEA MH026FJEA MH035FJEA MH052FJEA

FIXED

MH18VF1-09 MH19VF1-07 MH19VF1-12

OUTDOOR UNIT

FREE JOINT

MH040FXEA2B MH050FXEA2B MH060FXEA3B MH070FXEA4B MH080FXEA4B 

FIXED

MH18VF1X MH19VF1X


Display Explanation Main checking Point / Remark
E1↔01 Communication error (unable to receive data) Communication cable connection 
E1↔02 Communication error (outdoor cannot communicate) Another indoor unit or indoor PCB
E1↔21 Indoor unit room temperature sensor error (Open/Short) Room temperature sensor, indoor PCB
E1↔22 Indoor unit heat exchanger in temperature sensor error (Open/Short) Heat exchanger in sensor, indoor PCB
E1↔23 Indoor unit heat exchanger out temperature sensor error (Open/Short) Heat exchanger out sensor, indoor PCB
E1↔28 Indoor unit heat exchanger in temperature sensor detached Heat exchanger in senso
E1↔29 Indoor unit heat exchanger out temperature sensor detached Heat exchanger out sensor
E1↔30 Indoor unit heat exchanger in & out temperature sensor detached Heat exchanger in & out sensor
E1↔53 Indoor unit float switch second detection -
E1↔54 Indoor unit fan motor malfunction Fan motor and cable
E1↔61 More than 2 indoor units cool and heat simultaneously Another indoor unit operation mode
E1↔62 EEPROM error Indoor PCB
E1↔63 Option code setting error Option code
E1↔85 Cable miss-wiring Cable connection (Indoor & Outdoor unit)
E1↔86 MPI error malfunctio MPI
E2↔01 The number of indoor unit mismatched Cable connection (another indoor unit & outdoor unit), SW01(outdoor)
E2↔51 Compressor discharge sensor error(Short/Open) Outdoor unit
E5↔59 Outdoor unit error Outdoor unit (Error code)

Outdoor Unit

(The error indicated on the PCB display of outdoor unit)

INDOOR UNIT MH026FNCA, MH035FNCA, MH052FNCA, MH026FECA, 

MH035FECA, MH052FECA, 

OUTDOOR UNIT MH050FXCA2AMH080FXCA4A

Display Explanation (The error indicated on the PCB display of outdoor unit) Remark
E1 01 Communiaction error(indoor unable to receive data) Check electrical connection and setting
E1 02 Outdoor unit communication error (Abnormal data from indoor unit over 60 packet) Check electrical connection and setting
E1 21 Indoor unit room temperature sensor error (Open/Short)  
E1 22 Indoor unit heat exchanger in temperature sensor error (Open/Short)  
E1 28 Indoor unit heat exchanger out temperature sensor error (Open/Short)  
E1 29 Indoor unit sensor error-Evaporator pipe in sensor - Self diagnosis  
E1 88 Indoor unit sensor error-Evaporator pipe out sensor - Self diagnosis  
E1 54 Indoor Unit FAN Error  
E1 61 More than two indoor units cool and heat simultaneously  
E1 62 Indoor Unit EEPROM Error  
E1 63 Indoor Unit EEPROM Option Error  
E1 90 Failure of pipe check operation Check electrical connection and setting
E1 99 No pipe check operation check - occasion : try to operation after the installation through auto addressing mode without pipe check operation Check setting
E2 01 The number of Indoor unit mismatched  Check electrical connection and setting
E2 02 Communication error between the outdoor and indoor unit Check electrical connection and setting
E2 03

Outdoor communication error between main PCB

and sub PC

 
E2 21 Outside temperature sensor error(Short/Open) - Error level: over 4.9V(-50˚C) under 0.4V(93˚C  
E2 37 Condenser temperature sensor error(Short/Open) - Error level: over 4.9V(-50˚C) under 0.4V(93˚C  
E2 46 Outdoor unit sensor error - Condenser out sensor(Short/Open) - Self diagnosis  
E2 51 Compressor Discharge temperature sensor error  
E2 61 Compressor discharge sensor detached - Self diagnosis  
E3 20 Compressor OLP sensor error (Short/Open) - Error condition : outdoor temperature under -20˚C - Error level : over 4.95V(-30˚C) under 0.5V(151˚C)   

Outdoor Unit(cont.)

Display Explanation (The error indicated on the PCB display of outdoor unit) Remark
E4 01 Outdoor unit freezing(Compressor stop) check pipe lenght, indoor unit filter, refrigerant leakage/ charge and service port
E4 04 Outdoor unit overload - Safety control(Compressor stop) check pipe lenght, refrigerant leakage/charge
E4 16 Outdoor unit high discharge temperature - Safety control (Compressor stop) check pipe lenght, refrigerant leakage/charge
E4 19 Outdoor unit EEV open (Stopped indoor unit s) -Self diagnosis  
E4 22 Outdoor unit EEV open (operating indoor unit s) -Self diagnosis  
E4 40 High temperature(over 30˚C) of outdoor as heating mode  
E4 41 Low temperature(under -10˚C) of outdoor as cooling mode  
E4 58 Outdoor Fan Erro  
E4 60 Communication cable mismatched between indoor and outdoor unit Check electrical connection 
E4 61 Inverter compressor starting failure (5 times)  
E4 62 Compressor trip by input current control mode (PFC over current)  
E4 63 Compressor trip by OLP temperature control mode  
E4 64 DC peak error (IPM Over Current)  
E4 65 Compressor Vlimit Error  
E4 66 DC link Voltage error (under 150V, over 410V  
E4 67 Abnormal compressor running (Compressor Rotation Error)  
E4 68 Current sensor error  
E4 69 DC link Voltage sensor error   
E4 71 OTP Erro  
E4 72 Inverter micom zero-crossing error  
E5 54 NO GAS error(self diagnosis) Piping(gas leak)

SPLIT-TYPE AIR CONDITIONER

MODEL :

AR09TXFYAWKNEU, AR12TXFYAWKNEU, AR09TXHZAWKNEU AR12TXHZAWKNEU,

 AR09TXFYAWKXEU, AR12TXFYAWKXEU AR09TXHZAWKXEU, AR12TXHZAWKXEU

C101, C102 Communication error

C108 Set address error

C121 Room TH sensor error

C122, C123 INDOOR MID, INDOOR IN EVA-TH sensor error

C140 Dust sensor error

C142 Humidity error

C143 Motion sensor error

C154 Fan error(indoor)

C161 Mixed operation error

C163 Option error

C187 K1 filterfeed back error

C665 Drain pump error

*Note* If the set doesn’t work (No power), check the thermal fuse of terminal block OPEN or SHORT with Multimeter. * Measure the thermal fuse housing PIN#1~2 : OPEN(disconnection)-> defective product

SAMSUNG SPLIT-TYPE AIR CONDITIONER ERROR MODE
SAMSUNG SPLIT-TYPE AIR CONDITIONER ERROR MODE
Comments: 1
  • #1

    moarasbi (Monday, 10 June 2024 12:46)

    h6 error